How to carry out the hydraulic test of plate heat exchanger

09-12-2020

When the plate heat exchanger is repaired or clearly reassembled (replacement of heat exchanger gaskets, replacement of heat exchanger plates), the plate heat exchanger pressure test is required before use.

The main purpose is to check whether the plate heat exchanger is properly assembled and whether there is any leakage.

The correct water pressure test method is as follows:

First, check whether the clamping size of the plate heat exchanger meets the requirements of the drawing;

Second, fill with water or other fluids and exhaust air;

Third, install the blocking plate;

Fourth, connect the pressure test pump or other manual pressure test device;

Fifth, it is qualified to press and maintain pressure on one side alternately at 1.25 times the design pressure for 30 minutes without leakage. But the main thing is: the pressure should rise slowly and evenly to the required index when suppressing.

The above is the general process of a hydraulic test, you can make a reference. If there is a leakage problem during the hydraulic test of the plate heat exchanger, it is necessary to find out the cause and solve it before putting the plate heat exchanger into use.

Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy